Hempacore One is a one component, solvent-borne, physically drying intumescent coating for passive fire protection of structural steel against cellulosic fires in a wide range of fire durations. It is suitable for in-shop and on-site applications, interior and exterior use.
Recommended use
As intumescent fire protection for structural steel in interior and exterior conditions, up to Type X (EAD350402-00-1106 / EN 16623) and C4 conditions (ISO 12944-2). Suitable for I section beams, H columns, hollow sections and cellular beams.
As a repair and touch-up coating for damaged areas of freshly applied Hempacore One .
Certificates / Approvals
Features
Flash point: 23°C [73°F]
VOC content
Legislation | Value |
---|---|
EU | 320 g/L [2.67 lb/US gal] |
US (coatings) | 320 g/L [2.67 lb/US gal] |
US (regulatory) | 320 g/L [2.67 lb/US gal] |
China | 320 g/L [2.67 lb/US gal] |
According to ISO 11890-1. ªEU Directive 2004/42/CE. According to specific legislation, see details in the Explanatory Notes available at Hempel website, hempel.com or at your local Hempel website.
Handling
Handle with care. Before and during use, observe safety labels on packaging and paint containers and follow all local and national safety regulations. Always consult Hempel’s Safety Data Sheet for this product along with the Product Data Sheet.
For professional use only.
Product code: 43600
Standard shade / code: White 10000
Gloss: Flat
Volume solids: 75 ± 3%
Specific gravity: 1.3 kg/L [11 lb/US gal]
Cleanliness
Maintenance and Repair
Thinner
Not Recommended
Cleaner
Hempel’s Thinner 08080
Hempel’s Tool Cleaner 99610
Application method
Tool | Application parameters |
---|---|
Airless spray | Nozzle pressure: 200 bar [2900 psi]
|
If brush or roller application is used, more coats will be necessary to achieve the specified dry film thickness. In general, thinning is not recommended. Spray data are indicative and subject to adjustment. Pressure is for a material temperature of 20°C [68°F].
Film thickness
The film thickness is dependent on the required fire resistance as well as the massivity factor (Hp/A) of the steel element. Please contact your local Hempel representative. The maximum thickness per coat is 1500 micron [60 mils] Dry Film Thickness equivalent to 2000 micron [80 mils] Wet Film Thickness. Please consult the Application Instruction for more detailed information.
Application conditions
Application remarks
Product compatibility
Overcoating details
Shelf life
Ambient temperature | Product |
---|---|
25°C [77°F] | 15 months |
Shelf life from date of production, when stored in original, unopened containers. Thereafter, the product quality must be re-inspected. Storage at elevated temperatures may reduce shelf life. For advice, please consult Hempel.
Storage conditions
Product Data Sheet – Hempacore One
Issued by Hempel A/S – May 2025
Document Version: 4/4
Source: https://www.hempel.com
Technical Guidelines and Explanatory Notes
Last accessed: 28 May 2025