PRODUCT DATASHEET
Product characteristics
Recommended use
Hempacore AQ is recommended as an intumescent fire protection for structural steel in interior use up to Type Y conditions (EAD350402-00-1106 / EN 16623) and C2 conditions (ISO 12944-2). It is suitable for I-section beams, H columns, hollow sections and cellular beams. It can also be used as a repair and touch-up coating for damaged areas of freshly applied Hempacore AQ.
Service temperature:
Certificates / Approvals
- CE marked product with European Technical Assessment (ETA) ETA 13/1054. Up to 90 minutes.
- Assessed according to EN 13381-8, fire resistance of structural steel
- Assessed according to EN 13381-9, fire resistance of structural steel (cellular beams) Up to 60 minutes.
- Third-party verified, product-specific Environmental Product Declaration (Type III EPD, ISO 14025, EN 15804)
- Third party certified by Applus+; Fire Safety Mark
- Tested and assessed according to BS 476-21: Standard for Fire Test on Building Materials and structures; determination of the fire resistance of loadbearing elements of construction.
- Reaction to fire tested (as part of a coating system with approved primer and topcoat) according to EN13501-1
Features
- Excellent DFTs for open sections at 60 minutes
- Increased productivity thanks to high DFT per coat and faster drying, thus providing the required fire protection in less coats, reduced application costs and faster process time.
- Suitable for both open, closed and cellular beams steel structures.
- Tested and approved according to EN13381-8 for up to 90 minutes fire protection. It has ETA with 3rd party verified CE mark. It has BS-476 Assesment for up to 90 minutes fire protection with ApplusFire certificate.
- Environmental Product Declaration with third-party certification available (Type III EPD, acc. to ISO 14025, EN 15804). Product can contribute to EPD credits for LEED and BREEAM projects.
- Complies with EU Directive 2004/42/EC, The Paints Directive on the limitation of volatile organic compounds: subcategory
Product safety
Flash point 180°C [356°F]
VOC content
Legislation |
Value |
EU |
0 g/L [0.00 lb/US gal] |
US (coatings) |
29 g/L [0.24 lb/US gal] |
US (regulatory) |
43 g/L [0.36 lb/US gal] |
China |
0 g/L [0.00 lb/US gal] |
According to ISO 11890-2.
Handling
Handle with care. Before and during use, observe safety labels on packaging and paint containers and follow all local and national safety regulations. Always consult Hempel’s Safety Data Sheet for this product along with the Product Data Sheet.
For professional use only.
Product data
Product code: 48860
Standard shade / code: White 10000
Gloss: Flat
Volume solids: 73 ± 3%
Specific gravity: 1.5 kg/L [12 lb/US gal]
Surface preparation
Cleanliness
- Remove salts, detergents and other contaminants by high pressure fresh water cleaning.
- Abrasive blasting to min. Sa 2½ (ISO 8501-1) / SP 10 (SSPC).
- Zinc coated surfaces: use non-metallic blast media (corundum, garnet, etc.).
- Use approved primer.
- Remove oil, grease and other contaminants by suitable detergent cleaning.
- Remove dust, blast media and loose materials.
- The surface must be dry and clean prior to application.
- For approved substrates other than Carbon Steel, the substrate may require other surface preparations, consult Hempel’s application instructions for detailed information.
- Minor areas can be cleaned by power tool to St 3 provided the surface is roughened and not polished.
- Consult Hempel’s separate Surface Preparation Guidelines for more details.
Maintenance and Repair
- Minor areas may be hand or power tool cleaned instead of abrasive blasting.
Consult Hempel’s separate Surface Preparation Guidelines for more details.
Application
Thinner
Not Recommended
Cleaner
Fresh water
Application method
Tool |
Application parameters |
Airless spray |
Nozzle pressure: 200 bar [2900 psi] |
| Nozzle orifice: 0.017-0.023" |
If brush or roller application is used, more coats will be necessary to achieve the specified dry film thickness. In general, thinning is not recommended. Spray data are indicative and subject to adjustment. Pressure is for a material temperature of 20°C [68°F].
Film thickness
The film thickness is dependent on the required fire resistance as well as the massivity factor (Hp/A) of the steel element. Please contact your local Hempel representative. Please consult the Application Instruction for more detailed information. The maximum thickness per coat is 800 micron [32 mils] Dry Film Thickness equivalent to 1100 micron [43 mils] Wet Film Thickness.
Application conditions
- To avoid condensation, apply on a clean and dry surface with a temperature that is at least 3°C [5°F] above the dew point.
Relative Humidity:
- Relative humidity must be below 85% during curing.
Application remarks
Drying and overcoating
Product compatibility
- Previous coat: According to Hempel’s Specification. Only Hempel approved primer. Consult Hempel representative for information on approved primers.
- Subsequent coat: According to Hempel’s Specification. A selection of approved topcoats is available. Consult Hempel representative for information on approved topcoats.
Overcoating details
- Please consult the specific Drying time and Overcoating details for this product.
- Consult Hempel for specific details
- A topcoat cannot be applied before the specified intumescent thickness has been achieved and the coating is sufficiently dry. Consult Hempel representative for more detailed information.
Storage
Shelf life
Ambient temperature |
Product |
25°C [77°F] |
12 months |
Shelf life from date of production, when stored in original, unopened containers. Thereafter, the product quality must be re-inspected. Storage at elevated temperatures may reduce shelf life. For advice, please consult Hempel.
Storage conditions
- Temperature must not go below 5°C [41°F] during transport and storage.
- In case shelf life is exceeded, the product must be re-evaluated before use. Please contact a Hempel representative.
References
Product Data Sheet – Hempacore AQ
Issued by Hempel A/S – June 2025
Document Version: 4/4
Source: https://www.hempel.com
Technical Guidelines and Explanatory Notes
Last accessed: 28 May 2025
Reference link: https://www.hempel.com/service-and-support/technical-guidelines
Note: Always consult the latest version of the Product Data Sheet and associated documents directly from Hempel’s official website to ensure accuracy and compliance with the most current recommendations.